What the standard covers
EN 17037 sets out principles for an adequate subjective impression of brightness from daylight and an adequate view out, and contains recommendations on the duration of sunlight exposure in occupied rooms. The German 2022-05 edition replaces the 2019 version [1]. The standard distinguishes three levels – minimum, medium and high; the minimum recommended level should be stated [1].
Daylight provision: the three levels
For daylight openings in vertical and inclined surfaces [2]:
| Level | Target ET on 50 % of the area | Minimum target ETM on 95 % of the area | Share of daylight hours |
|---|---|---|---|
| Minimum | 300 lx | 100 lx | 50 % |
| Medium | 500 lx | 300 lx | 50 % |
| High | 750 lx | 500 lx | 50 % |
A level is achieved when both conditions are met simultaneously [2]. Proof is provided by calculation, either using climate data for the location or, in simplified form, via the daylight factor.
The other criteria
- View out: assesses viewing angle, viewing distance and the number of visible layers (sky, landscape/buildings, ground).
- Sunlight exposure: recommendation on how long an occupied room should receive direct sunlight on a reference day – relevant for homes, hospital rooms and nurseries, for example.
- Glare protection: protection against glare from the sun and sky, usually via solar and glare protection systems.
| Level | View: horizontal sight angle / outside distance / layers | Sunlight exposure on the reference day | Glare protection (DGP, exceeded for max. 5 % of usage time) |
|---|---|---|---|
| Minimum | ≥ 14° / ≥ 6 m / 1 | ≥ 1.5 h | 0,45 |
| Medium | ≥ 28° / ≥ 20 m / 2 | ≥ 3 h | 0,40 |
| High | ≥ 54° / ≥ 50 m / 3 | ≥ 4 h | 0,35 |
Compiled from [2] [3]; the view criteria each apply to at least 75 % of the used floor area [2].
The reference day for sunlight exposure can be chosen between 1 February and 21 March; the reference point is at least 1.2 m above the floor and 0.3 m above the window sill [2]. Since DIN 5034-1 was withdrawn, LiTG recommends the "minimum" level as the minimum requirement for sunlight exposure, and the "medium" level of 3 hours for living rooms, children's rooms and day-care centres [4]. Glare is assessed using the daylight glare probability DGP in an annual simulation [5].
Why early planning is decisive
Window size, room depth, sill height, glazing and shading by neighbouring buildings determine daylight quality. These parameters are defined in preliminary and concept design. A daylight simulation at this stage shows whether the agreed level is achieved and avoids costly rework. At the same time, the need for artificial light – and therefore energy consumption – can be reduced.
Frequently asked questions
Is EN 17037 mandatory?
The standard is not automatically part of building regulations. It becomes binding when agreed contractually or required by certification systems.
Which level makes sense for homes?
The standard does not specify this. In practice, at least the "minimum" level is often aimed for in occupied rooms; the decision is made for each project.
Sources (in German)
- Baunormenlexikon – DIN EN 17037:2022-05
- FVLR – Leitfaden DIN EN 17037
- REHVA Journal – EN 17037 a step forward
- LiTG-Publikation 53 – Planungshinweise Innenraumbeleuchtung und Tageslicht
- Deutsches Architektenblatt – Tageslicht nach DIN EN 17037
Author: Paul Rostand Ndjeundoun, M.Sc. (Hons), Certified Lighting Expert (LiTG), Registered European Lighting Expert · As of November 2026. Standard values have been carefully researched but do not replace consulting the currently valid edition of the standard.